What is an RCD and what does it do?
1.
An RCD is defined, in BS 7671, as:
‘A mechanical switching
device or association of devices intended to cause the opening of the contacts
when the residual current attains a given value under specified conditions’.
An RCD is a protective device used to automatically
disconnect the electrical supply when an imbalance is detected between live
conductors.
In the case of a single-phase circuit, the device
monitors the difference in currents between the phase and neutral conductors.
In a healthy circuit, where there is no earth fault current or protective
conductor current, the sum of the currents in the phase and neutral conductors
is zero.
If a phase to earth fault develops, a portion of the
phase conductor current will not return through the neutral conductor. The
device
monitors this difference, operates and disconnects the
circuit when the residual current reaches a pre-set limit, the residual
operating current (IDn).
RCDs are used to provide protection against the
specific dangers that may arise in electrical installations including:
> Protection
against indirect contact
> Supplementary
protection against direct contact
> Protection
against fire and thermal effects
An RCD on its own does not provide protection against overcurrent’s.
Overcurrent protection is provided by a fuse or a miniature circuit-breaker
(MCB).
However, combined RCD and MCBs are available and are
designated RCBOs.
2. Types of RCDs
RCD
is the generic term for a device that operates when the residual current in the
circuit reaches a predetermined value.
2.1 Older installations with ELCBs
Historically,
two basic types of earth leakage circuit-breaker (ELCB) were recognised by the
Regulations; the familiar current-operated type and the earlier
voltage-operated type. The voltage-operated type ceased to be recognised by the
Regulations in 1981and today, only the current-operated type is recognised. The
voltage operated device can be distinguished by its two separate earthing
terminals– one for the connection of the
earthing
conductor of the installation and the other for a connection to a means of
earthing. Such devices were often used on installations forming part of a TT
system where the means of earthing was an earth electrode.
The
major drawback with the voltage operated earth leakage circuit-breaker is that
a parallel earth path can disable the
device.
2.2 Recognised devices
RCDs
are manufactured to harmonised standards and can be identified by their BS EN
numbers. An RCD found in an older
installation may not provide protection in accordance with current standards.
The following list identifies the applicable current standards:
> BS 4293 : 1983 (1993)
Specification for residual current operatedcircuit-breakers.
(Replaced by BS EN 61008-
1: 1995, BS EN 61008-2-1: 1995 and BS
IEC 61008-2-2: 1990). This Standard
remains current
> BS 7071 : 1992 (1998)
Specification for portable residual current
Devices
> BS 7288 : 1990 (1998)
Specification for socket-outlets incorporating
residual current devices. (SRCDs)
> BS EN 61008-1 : 1995 (2001)
Residual current operated circuit-breakers
without integral overcurrent protection for
household and similar uses (RCCBs)
> BS EN 61009-1 : 2004
Residual current operated circuit-breakers
with integral overcurrent protection for
household and similar uses (RCBOs)
2.3 Characteristics of RCDs
RCDs
are defined by a series of electrical characteristics, three main characteristics
are:
1.
The rating of the device in amperes, I.
2.
The rated residual operating current of the protective device in amperes, IDn.
3.
Whether the device operates instantaneously or incorporates an intentional time
delay to permit discrimination. Such devices are called ‘S’ or Selective.
Devices
are manufactured with different values of rated current and rated residual
operating current but we will just consider the rated residual operating
current of the protective device in amperes, IDn.
3. Applications
The
correct device must be selected for the particular application. Choosing the
wrong device could have serious consequences and could result in electric shock
or fire.
3.1 Unwanted tripping
Unwanted
tripping of RCDs can occur when a protective conductor current or leakage
current causes unnecessary operation of the RCD.
An
RCD must be so selected and the electrical circuits so subdivided that any
protective conductor current that may be expected to occur during normal operation
of the connected load(s) will be unlikely to cause unnecessary tripping of the device (Regulation
531-02-04 refers). Such tripping can occur on heating elements, cooking appliances
etc., which may have elements that absorb a small amount of moisture through
imperfect element end seals when cold. When energised, this moisture provides a
conductive path for increased leakage and could operate the RCD. The moisture
dries out as the element heats up. Although not precluded in BS 7671, it is not
a requirement to use an RCD on such circuits if other satisfactory means of protection
are available.
Providing
an RCD with a higher rated residual operating current may solve the problem but
the requirements of the Regulations would still have to be met.
3.2 Discrimination
Where
two, or more, RCDs are connected in series, discrimination must be provided, if
necessary, to prevent danger (Regulation 531-02-09 refers). During a fault,
discrimination will be achieved when the device electrically nearest to the
fault operates and does not affect other upstream devices.
Discrimination
will be achieved when ‘S’ (Selective) types are used in conjunction with
downstream general
type
RCDs. The ‘S’ type has a built-in time delay and provides discrimination by
simply ignoring the fault for a set period of time allowing more sensitive downstream
devices to operate and remove the fault.
For
example, when two RCDs are connected in series, to provide discrimination, the
first RCD should
be
an ‘S’ type. RCDs with built in time delays should not be used
4. Labelling
Regulation
514-12-02, states that:
“Where an installation incorporates a residual
current device a notice shall be fixed in a prominent position at or near the
origin of the installation. The notice shall be in indelible characters not smaller
than those here illustrated and shall read as follows:”
|
5. Testing
RCDs
must be tested. The requirements are stated in the following Regulations:
a.
The effectiveness of the RCD must be verified by a test simulating an appropriate
fault condition and independent of any test facility, or test button,
incorporated in the device (Regulation 713-13-01)
b.
Where an RCD of 30mA provides supplementary protection the operating time must
not exceed 40 ms at a residual current of 5 IDn.
(Regulation
412-06-02 refers) Tests are made on the load side of the RCD between the phase
conductor of the protected circuit and the associated cpc. Any load or
appliances should be disconnected prior to testing. RCD test instruments
require a few milliamperes to operate; this is normally obtained from the phase
and neutral of the circuit under test.
When
testing a three-phase RCD protecting a three-wire circuit, the instrument’s
neutral is required to be connected to earth. This means that the test current
will be increased by the instrument supply current and
will
cause some devices to operate during the 50% test, possibly indicating an
incorrect operating time. Under this circumstance it is necessary to check the
operating parameters of the RCD with the manufacturer before failing the RCD.
5.1 Range of tests
5.2 Integral test device
An
integral test device is incorporated in each RCD. This device enables the
mechanical parts of the RCD to be
Verified
by pressing the button marked
‘T’
or ‘Test’.
6. Test Instrument
The
test instrument used to test RCDs should be capable of applying the full range
of test current to an in- service accuracy, as given in BS EN 61557-6.
This
in-service reading accuracy will include the effects of voltage variations
around the nominal voltage of the tester. To check RCD operation and to
minimise danger during the test, the test current should be applied for no
longer than 2s. Instruments conforming to BS EN 61557-6 will fulfil the above requirements.
■
Device Instrument test current setting Satisfactory
result
General purpose RCDs to BS 4293 and RCD protected
socket-outlets to BS 7288
50% of operating current Device should not operate 100% of
operating current Device should operate in less than 200ms. Where the RCD incorporates
an intentional time delay it should trip within a time range from 50% of the
rated time delay plus 200ms’ to 100 % of the rated time delay plus 200ms
General purpose RCCBs to BS EN 61008 or RCBOs to BS
EN 61009
50% of operating current Device should not operate 100% of
operating current Device should operate in less than 300ms unless it is of ‘Type
S’ (or selective) which incorporates an intentional
time delay. In this case, it should trip within a time range from
130ms to 500ms
Supplementary protection against direct contact IDn ≤ 30mA
Test current at 5 IDn. The maximum test time must not be longer than 40ms, unless
the protective conductor potential does not exceed 50V. (The instrument
supplier will advise on compliance).
Device should operate in less than 40ms.
I hope this overview will be of service to others, for further
information do not hesitate to contact me directly from our website www.safe-electric.com or by E-Mail : - enquiries@safe-electric.com
Whether the device operates instantaneously or incorporates an intentional time delay to permit discrimination. Such devices are called ‘S’ or Selective. click here
ReplyDelete